HS-AC22K

PV-Driven Air-Cooled Chiller

Start with the application.

The HS-AC22K is a 22kW-class PV-driven air-cooled chiller whose core logic lets PV DC bypass the DC-AC-DC conversion chain and feed directly into the compressor's DC bus. A variable-speed scroll compressor adjusts continuously with PV output; PV direct-drive utilization reaches over 98%, cutting 6%-8% conversion loss versus a PV plus conventional air conditioner combination. R32/R290 low-GWP refrigerant and a -10°C to +50°C wide operating range allow deployment across climates from cold to hot. A residential 22kW and a commercial 45kW cooling configuration cover hourly cooling loads for small businesses, process cooling and large public buildings. The reserved heat-recovery interface turns waste heat from refrigeration into usable hot water, further reducing primary energy consumption.

Technical information

ParameterValue
Refrigeration
Cooling Capacity (Residential / Commercial)22 kW / 45 kW
Estimated Electric Power (Residential / Commercial)5.6 kW / 11.2 kW
Daily Cooling Demand (Residential / Commercial)72 kWh / 134 kWh
COP (Rated, Residential)3.93
COP (Rated, Commercial)4.02
Part-Load Efficiency (IPLV)5.2 (residential) / 5.5 (commercial)
Compressor
TypeVariable-speed scroll
Speed Range1800-7200 rpm
Capacity Regulation15%-100% stepless
Starting MethodSoft start, no inrush current
Refrigerant & Condensing
RefrigerantR32 / R290
GWP (R32 / R290)675 / 3
Condensing MethodAir cooling
Airflow (Residential / Commercial)8500 / 16000 m³/h
Fan TypeEC variable-frequency axial fan
PV Integration
ConnectionPV direct drive + storage assist
Max. PV Input Power (Residential)8 kWp
Max. PV Input Power (Commercial)16 kWp
PV DC Voltage Range200-750 Vdc
PV Direct-Drive Utilization≥98%
Control StrategyDynamic MPPT load tracking, compressor follows PV output
Operating Range
Ambient Temperature-10°C to +50°C
Chilled Water Temperature Range5-18°C
Altitude≤2000 m
Heat Recovery
InterfaceReserved (heat exchanger / hot water connection)
Recoverable Heat (Residential / Commercial)Approx. 22 / 45 kW (condensing side)
Electrical
Grid Auxiliary Power Supply380-415 Vac / 50 Hz, three-phase
Standby Power<20 W
CommunicationModbus TCP / RS485
Mechanical
Dimensions (Residential / Commercial)1800×1400×900 / 2200×1800×1100 mm
Weight (Residential / Commercial)420 / 780 kg
InstallationRoof / ground, vibration-isolation pads standard
Certification
Safety & Grid-TiedCE · IEC 60335-2-40

Let’s shape your next energy step.

Share your questions or project needs with the HESEN team.

Request consultation